Live · Scanning Check #042 · Started 14:32

Stage 2C tender pack — multi-discipline scan

161 files · 560 pages of specs · Corpus v.2026.05 · Tier 2 (Mid) · est. €400 · 4-hour turnaround

Total findings
327
+12 in last hour
CRITICAL
30
Verify before issue
HIGH
144
Worth reviewing
MEDIUM
116
Hygiene fixes
LOW
37
Notes for record

5 disciplines · parallel

Live
Architectural 142 findings · 100%
Civil & Structural 53 findings · 100%
Mechanical 72 findings · 100%
Electrical 47 / ~62 · 76%
Fire 13 / ~18 · 42%
Elapsed
2:48:12
Remaining
~52m
Conf
96.2%

Inference cost

Input tokens 1,432,810
Output tokens 487,224
Cheap routing 42% saved
Running cost €17.42
Billed (Tier 2) €400.00
ID
Sev
Issue · 1-sentence
Element · Standard
Source
A-303
CRIT
K10 metal-stud partitions specified REI 30 only — no REI 60 compartment-wall type in spec body.
Wall · TGD-B 2024 §3.5.5
Arch Spec p.58
SD-001
CRIT
Windows & External Doors Schedule AR-40002 contains stair-section drawings, not window schedule.
Schedule · I.S. EN 14351-1
AR-40002
S-008
CRIT
Foundation design on blank "undisturbed and firm soil" — no GI report, no bearing pressure stated.
Foundation · EN 1997
11001 p.1
E-103
CRIT
Lightning Protection §12.20 describes a 2-storey school in Ballina — wrong project, wrong building type.
Lightning · IEC 62305
Elec Spec p.78
M-200
CRIT
Fire and smoke dampers specified to BS 476 Part 8:1972 (withdrawn) — CE-marking requires IS EN 15650.
Fire damper · IS EN 15650
Mech Spec §5.02
S-207
HIGH
SW attenuation calc methodologically flawed; 75mm orifice passes more than declared 2 l/s.
Drainage · GDSDS
SW Att xlsx
E-212
HIGH
Form of Tender VAT lines include 13.5% and 21% — correct Irish standard rate is 23% since 2024.
Pricing · Revenue VAT
FoT Sch.1
M-203
HIGH
No HSE L8 / HTM 04-01 Legionella regime — only one-off chlorination at handover specified.
Plumbing · HTM 04-01
Mech Spec §9
A-302
HIGH
Arch spec cites UK Approved Documents K and M, NJUG, UK supplier addresses — UK NBS-Chorus export.
Spec · BCAR SI 9/2014
Arch Spec p.12
F-001
HIGH
FSC Condition 2 requires IS 3218:2024 — spec body cites IS 3218:2013 (superseded). Update required.
Fire alarm · IS 3218:2024
FSC + Elec §12
M-201
MED
Mech spec contains "Twin Wall Pressurised Flue" and "for each dwelling" references — residential gas legacy in heat-pump project.
Spec · NBS Chorus
Mech Spec §3
S-200
MED
C&S spec references basements, lift pits, swimming pools, underpinning — none exist in this single-storey project.
Spec · NBS Chorus
CS Spec §H
315 more findings · use filters above to narrow
Showing 12 of 327 · Auto-refresh on
1